6 Operating status messages
BU 0155 en-3520 99
6.4 FAQ operational problems
Fault Possible cause Remedy
Device will not start (all LEDs
off)
No mains voltage or wrong mains
voltage
Devices without integrated mains unit
(Option HVS): No 24 V DC control
voltage
Check connections and supply
cables
Check switches / fuses
Device does not react to
enabling
Control elements not connected
Right and left enable signals present
simultaneously
Enable signal present before device
ready for operation (device expecting a
0 1 flank)
Restart inhibit is active
Blocking time for reversing is active
Reset enable
Change over P428 if
necessary: "0" = device
expects a 01 flank for enable
/ "1" = device reacts to "Level"
Danger: Drive can start up
independently!
Check control connections
Check P130
Check DIP switch S2-DIP1
Motor will not start in spite of
enable being present
Motor cables not connected
Brake not ventilating
Check connections and supply
cables
Device switches off without
error message when load
increases (increased
mechanical load / speed)
Mains phase missing
Check connections and supply
cables
Check switches / fuses
Motor rotating in wrong
direction
Motor cable: U-V-W interchanged
Motor cable Switch 2 phases
Alternatively:
Swap parameter P420
functions right / left enable
Table 6: FAQ operational problems