NORDAC LINK (SK 155E-FDS / SK 175E-FDS) – Users Manual for Motor Starters as Field Distributors
72 BU 0155 en-3520
The ParameterBox SK PAR-3H must have at least software version 4.6 R1.
The individual parameters are functionally combined in groups. The first digit of the parameter number
indicates the assignment to a menu group:
Menu group No. Master function
Display of parameters and operating values
Basic device settings, e.g. on/off switching behaviour
Electrical settings for the motor (motor current or starting voltage (starting
voltage))
(P3--) Settings for the integrated PLC
Assignment of functions for the inputs and outputs
parameters
Priority monitoring function and other parameters
(P7--) Display of operating values and status messages
Factory setting P523
Use the parameter P523 to load the factory setting of the entire parameter set. The restoration of the
factory settings (P523) affects all parameters. Check the motor data afterwards and readjust them if
needed.
Furthermore, the potentiometers (P1-P3) and the DIP switch (S1, S2) are reactivated.