NORDAC LINK (SK 155E-FDS / SK 175E-FDS) – Users Manual for Motor Starters as Field Distributors
88 BU 0155 en-3520
P580 Error in the event of overtemp. RF
Other applicable parameter(s): P108, P427
Fault shut-off due to overtemperature – selection of whether an over temperature error
(PTC) should lead to a warning or a fault shut-off.
Value Meaning
Warning (
) due to overtemperature
Fault message (E002) and shut-off of device due to
overtemperature
P581 Phase sequence detection RF
Other applicable parameter(s): P130, P428
Analysis of phase sequence of supply network by the device and automatic adaptation
of rotary field of motor to the required direction of rotation.
As long as parameter P130=0 is set, phase sequence detection is determined via the
DIP switch S2-DIP2. In this case the parameter can only be read, but not changed. It
then corresponds to the setting that is determined by the DIP switch.
Value Meaning
0 Off
The direction of rotation of the motor is determined by the direction
of rotation of the supply network.
1 On
The direction of rotation of the motor is determined by the enable
direction.
P582 Manual brake release RF
Other applicable parameter(s): P420
Definition of conditions for releasing a connected electro-mechanical brake
DANGER! With certain drive tasks (e.g. lifting gear) it can be dangerous to release of
the brake without the drive running (risk of raised load falling)!
Value Meaning
The brake is only released if the motor is enabled.
The brake is released even if the motor has not been enabled (e.g.
if a drive is to be moved for revision work).