System Settings
System I/O
Output
OLED User Interface
79
Part 1128351_02
E 2020 Nordson Corporation
Assigning Light Tower Outputs
1. Select Output press > then select Light Tower.
2. Decide if you want to Invert (or reverse the polarity) of the Output. Select
Invert and press
to change the polarity. The default, is not inverted
(active high).
3. Use the Up key on the Navigation pad to select Assign, then press > to
view the output menu list selection. Use the Up/Down keys on the
Navigation pad to scroll through the list. Press to assign the output
selection you want. When done, press < to return to the Light Tower
menu.
4. Decide if you want to test the current output assignment. Select Test,
then press
to toggle Start/Stop the test.
5. Press
to return to the Home screen.
NOTES:
S You can assign the same output selection to multiple outputs.
S You can assign standard outputs using the Light Tower board.
S The System Alert and System Fault outputs are inverted by default,
although the Invert check box is clear.
S The default light tower output selections for the with the Legacy I/O
expansion kit are as follows:
Output 1 through 7: Disabled
Light Tower #2: System Fault
Light Tower #3: Tank Low
S The default light tower color associations are as follows:
White - Power On/Off
Green - System Ready
Red - Any Fault Alarm or Flashing Red for any Stop Alarm
Amber - Any Alert Alarm
Blue - Idle condition (Setback, Heating, Pump Off, Ready Delay)