400/480 Volt ProBlue Adhesive Melters
E-6
Part 1024496_06
2014 Nordson Corporation
Installation
Before installing the transformer, familiarize yourself with the Section 3,
Installation.
NOTE: ProBlue 400/480 volt transformers can only be used in conjunction
with ProBlue adhesive melters that are specifically designed for use with
440/480 volt electrical service.
Clearances
Figure E‐1 illustrates the minimum clearances that are required between the
melter and surrounding objects. Table E‐2 describes each clearance.
C
D
A
B
Figure E‐1 Minimum installation clearances (P4 top and front views shown)
Table E‐2 Installation Clearances
Item Description Required Clearance
A
The distance from the outside edge of a
5
/
16
‐inch Nordson hose
to the front face of the melter when a short 90‐degree hose
fitting is to connect the hose to the melter
P4 = 370 mm (14.5 in.)
P7 = 370 mm (14.5 in.)
P10 = 391 mm (15.4 in.)
B
The clearance required to open the pump enclosure door P4 = 243 mm (9.6 in.)
P7 = 243 mm (9.6 in.)
P10 = 268 mm (10.55 in.)
C
The distance from the melter sub‐base to the front edge of the
tank lid when the lid is at its highest point.
P4 = 575 mm (22.6 in.)
P7 = 637 mm (25.1 in.)
P10 = 729 mm (28.7 in.)
D
The clearance required on the left side of the melter to open the
electrical enclosure door or remove a hose/gun module.
P4 = 689 mm (27.1 in.)
P7 = 752 mm (29.6 in.)
P10 = 755 mm (29.7 in.)