Specifications Product Description
XPIQ PN 51013:C 7/01/03 11
1.3.3 XPIQ-SLI Signaling Line Interface
All screw terminal blocks accept wire up to 12 AWG (3.3 mm
2
).
Compatible with CLIP and FlashScan protocols
Average SLC current: 1.0 mA
SLC isolation: 500 VDC, limited by transient protection components to 40 VDC
Normally Open local trouble relay TB11 contact rating: 2 amperes @ 32 VDC (resistive)
Maximum length of local SLC loop wiring: 2,000 feet (600 m)
Maximum resistance of the local SLC (from any device to FACP): 50Ω
Maximum resistance of the local SLC (from any device to XPIQ-SLI): 20Ω (Maximum
number of detectors and modules = 64)
Maximum SLC local branch current degraded mode: 20Ω (See “Current Draw Tables for
Devices on the Local SLC Branch” in Section 2.5.3)
1.3.4 XPIQ-AIB4/AIB1 Audio Input Board (4 channel/1 channel)
All screw terminal blocks accept wire up to 12 AWG (3.3 mm
2
)
Nominal Input Voltage: 3.5 Vp (peak voltage)
1.3.5 XPIQ Audio Amplifiers
1.3.6 XPIQ-RMI Remote Microphone Interface
All screw terminal blocks accept wire up to 12 AWG (3.3 mm
2
)
Supply output voltage for RM-1(SA) TB2-1 (+24V), TB2-2 (common): 19- 28 VDC
Nominal audio level: 2.5 V
RMS
1.3.7 Entire Audio Path Characteristics
Complies with
• UL requirements - Frequency response: 450 Hz - 3.8 kHz
• ULC requirements - Frequency response: 400 Hz - 4 kHz
XPIQ-AA25 XPIQ-AA2270
Built-in short circuit and thermal
shutdown protection
✓✓
Nominal (sinusoidal) output voltage 25 V
RMS
70.7V
RMS
Nominal (sinusoidal) output power 25 W 22 W
Nominal (sinusoidal) output current 1 ampere 310 mA