Programming the XPIQ Programming
XPIQ PN 51013:C 7/01/03 67
3.6.6 Load XPIQ
Clicking the Load XPIQ button will display a screen with a variety of options which allow
programming the XPIQ from the PC. When the connection is made between the XPIQ and PC, the
XPIQ-SLI 7-segment LED Display will steadily display the letter b to indicate that the XPIQ is
connected to the PC and ready to receive any of the programmed options listed below.
The various options are accessed by clicking the appropriate button. The available options during
this mode of operation include the following:
• Boot Code - allows downloading of the selected boot program to the XPIQ
• Parameter - allows downloading of the selected parameter file to the XPIQ
• Application Code - allows downloading of the selected application program to the XPIQ
• SLI Boot - allows downloading of the selected boot program to the XPIQ-SLI
• SLI Application - allows downloading of the selected application program to the XPIQ-SLI
• Reset - disconnects the XPIQ from the PC and returns the XPIQ to an On Line condition