EasyManua.ls Logo

Omega i-SERIES - Alarm 1 Low (Command Index 12); Alarm 2 Configuration (Command Index 0 A)

Omega i-SERIES
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.7.6 Alarm 1 Low (Command Index 12)
Description: AL1LO.23~0 means 3 bytes x 8 bit positions of the Alarm Low Data
AL1LO.23 = AL1LO.22~20 = AL1LO.19~0 =
0 = positive sign 000 – Not Allowed Setpoint data
1 = negative sign 001 – Decimal Point 1 (FFFF.)
010 – Decimal Point 2 (FFF.F)
011 – Decimal Point 3*(FF.FF)
101 – Decimal Point 4*(F.FFF)
*Process only
Example:Set Alarm 1 Low value to -50.0
The command data is 101000000000000111110100Bin = A001F4Hex.
Send: *W12A001F4
To set the Decimal Point for proper position see command format for RDGCNF
(command index 08).
5.7.7 Alarm 2 Configuration (Command Index 0A)
Description: ALR2CNG.76543210 means 8 bit positions of the Command Data.
BIT NUMBER FUNCTION
76543210
0 Voltage Retransmission
1 Current Retransmission
0 0 Active Above
0 1 Active Below
1 0 Active Hi/Lo
1 1 Active Band (Deviation only)
0 Normally Open
1 Normally Closed
0 Unlatch
1 Latch
0 Absolute
1 Deviation
0 Disable
1 Enable
Example: Set Alarm 2 Enable, Absolute, Latch, N.O.,Above, Current Retransmission.
The command data is 10000101 Bin = 85Hex. Send: *W0A85
Warning: If you change the “0A” to “00” on units with Isolated Analog Output it
will disable the Alarm 2 menu.
26

Table of Contents

Related product manuals