133
CT Testing Using the Guesser Function
7.4 Running the Automatic Test
1. After switching the CT Analyzer on or after initializing a new test from the
main menu, the default CT-Object card is displayed.
Figure 7-1 Empty CT-Object card after initializing a new test
2. Enter as many name plate data as available. The full set of CT data includes:
I
pn
, I
sn
, standard, CT type (P/M), class and rated power of the CT (VA).
Note: If the "Check "*" settings before start" option is enabled in the default
test settings (see section 5.7.3 "Miscellaneous Settings" on page 70), no
automatic assessment will be available if you do not enter data for a
parameter that is relevant for assessment. Such parameters are marked by
a star "*".
3. Execute the CT test as described in section 4.3 on page 52.
If the "Display warning before start" option is enabled in the default test
settings (see section 5.7.3 "Miscellaneous Settings" on page 70), a warning
is displayed if you did not enter data for a parameter marked by a star "*".
Figure 7-2 "No assessment" warning displayed if you did not enter data for
a parameter relevant for assessment
Press Cont. Test to continue testing without an automatic assessment. Or
press Cancel Test and enter data for all parameters marked with a star "*"
in the CT-Object card and start the test again.