15
Introduction
Note: Please refer to the following sections for more information:
Section 2.3 on page 23 for information on how to connect the CT Analyzer to
a PC.
Chapter 5 on page 59 for general information on how to operate the
CT Analyzer.
Section 5.7 on page 65 for more detailed information about the
Setting Menu page.
1.2.5 Inputs and Outputs
Figure 1-5 Inputs and outputs of the CT Analyzer
Warning: While the red LED of the key is flashing, voltage is applied at
the output and the measurement inputs.
I/0
Output
Generator output.
AC: 40V
rms
, 5A
rms
DC: 120V, 15A
Sec
Measurement input for secondary side of CT,
150V
AC
max., 500kΩ input impedance
Prim
Measurement input for primary side of CT,
30V
AC
max., 150kΩ input impedance