139
Using the Quick Test Feature
8.3 Performing Measurements with Quick Test
Measurements using Quick Test are not automatically stopped by the
CT Analyzer. Such measurements have to be stopped manually by the
user.
Proceed as follows to perform measurements using the Quick Test feature:
1. Select New Quick-Test from the main menu and press the OK soft key to
open Quick Test. The display then shows the CT-Quick card.
Figure 8-2 CT-Quick card
2. Select the measurement type and connect your test object to the
CT Analyzer correspondingly (see sections 8.4 to 8.10 below).
3. Define your measurement quantities.
4. Start and stop your measurement by pressing the key.
5. After starting a measurement, the Results card is displayed automatically,
showing the measurement results.
8.4 Advanced Measurement
The Advanced measurement type offers complete multimeter measurement
functionality and free adjustment of all measurement quantities, such as AC or
DC signal output, voltage or current output, output frequency, measurement
mode (DC, RMS or frequency-selective) for the input, etc.
Using the Advanced measurement type it is also possible to use input "Sec" of
the CT Analyzer as a voltmeter for measuring external voltages up to
150V
RMS
with frequencies up to 4kHz.
Press the Main soft key in
any test card
Main Menu:
- New Quick-Test
OK soft key
-> CT-Quick card
How to get there:
Press the Main soft key in
any test card
Main Menu:
- New Quick-Test
OK soft key
CT-Quick card:
Measurement Type:
Advanced
How to get there:
Caution: When using Quick Test, input "Sec" of the CT Analyzer is able to
measure voltages up to 150V
RMS
. Do not connect voltages above 150V or
even mains voltages to the CT Analyzer inputs! This will damage the
CT Analyzer!