23
Measurement Setup
3.5 Additional Wiring for Burden Measurement
Burden measurement may be performed separately or in conjunction with CT
testing and/or primary winding resistance measurement.
The following wiring is required for burden measurement (in addition to the basic
measurement setup shown in Figure 3-2 and Figure 3-3 and/or the additional
wiring for primary winding resistance measurement shown in Figure 3-5, as
required).
Figure 3-4 Additional wiring required for burden measurement
X1
X2
X3
X4
X5
X6
*
*
Burden
Basic CT wiring,
see Figure 3-2 or Figure 3-3
CT
* For information how to connect the communication link between the CT SB2 and the
CT Analyzer, please refer to section 3.2 on page 20.