173
Error and Warning Messages
201.xxx Warning [201.xxx] Check connection. Measured ratio > 50000:1.
Reason: Measurement input "Prim" is possibly not connected properly.
Solution: Check whether the primary side measurement input "Prim" is connected
properly.
202.xxx Warning [202.xxx] Check connection. Polarity of input SEC and power output are not
the same.
Reason: Polarity of input "Sec" and "Output" are not the same.
Solution: Check whether the output generator ("Output") and measurement input "Sec"
are connected properly and with correct polarity.
203.xxx Warning [203.xxx] Check connection. Input SEC may be disconnected.
Reason: Input signal at input "Sec" differs from the expected one.
Solution: Check whether the output generator ("Output") and measurement input "Sec"
are connected properly.
204.xxx Warning [204.xxx] Check connection. Polarity of input PRIM and power output are not
the same.
Reason: Input signal at input "Prim" differs from the expected one: Reverse polarity at
input "Prim".
Solution: Check whether the output generator ("Output") and measurement input "Prim"
are connected properly and with correct polarity.
204.xxx Warning [204.xxx] Check CT SB2 switch box wiring: Wrong polarity at PRIM terminal.
Reason: Input signal at input "PRIM" differs from the expected one: Reverse polarity at
CT SB2 input "PRIM".
Solution: Check whether the PRIM IN sockets on the CT SB2 are connected properly
and with correct polarity. If necessary, connect with changed polarity.
205.xxx Warning [205.xxx] Check connection. Input PRIM may be disconnected.
Reason: Input signal at input "Prim" differs from the expected one.
Solution: Check whether the output generator ("Output") and measurement input "Prim"
are connected properly.
205.xxx Warning [205.xxx] Check CT SB2 switch box wiring: PRIM IN terminal may be
disconnected.
Reason: Input signal at input "Prim" differs from the expected one.
Solution: Check whether the PRIM IN sockets on the CT SB2 are connected properly.
206.xxx Warning [206.xxx] Check connection. Ensure that the output is connected to the
primary side of the CT.
Reason: Input signal at input "Prim" differs from the expected one.
Solution: Check that the output generator ("Output") is connected to the CT and that the
primary side of the CT is connected to input "Prim".
206.xxx Warning [206.xxx] Check CT SB2 switch box wiring: CTA OUTPUT and/or PRIM OUT
terminal may be disconnected.
Reason: Input signal at input "Prim" differs from the expected one.
Solution: Check whether the PRIM OUT and the PRIM IN sockets on the CT SB2 are
connected correctly to the primary side of the CT.
207.xxx Warning [207.xxx] Check connection! OUTPUT may be disconnected.
Reason: The current signal differs from the expected one.
Solution: Check whether the output generator ("Output") and measurement input "SEC"
are connected properly to the secondary side of the CT.