175
Error and Warning Messages
332.xxx Note [332.xxx] I-sn has to be specified. Vb and VA are calculated dependent on I-sn.
Reason: You tried to enter values for V
b
or VA without specifying the I
sn
value first.
Solution: Enter a valid I
sn
value before specifying values for V
b
and VA.
333.xxx Note [333.xxx] First define I-pn for this tap.
Reason: You tried to enter a nominal burden (VA) value for a tap without specifying the
I
pn
for this tap first.
Solution: Enter a valid I
pn
value for the tap before specifying the nominal burden (VA).
334.xxx Note [334.xxx] Test cannot be started. Nominal burden (VA) should be >= 3.75VA.
Reason: The nominal burden (VA) entered is lower than the limit specified in the device
settings (parameter "Min. VA at M cores Isn 5A").
Solution: Enter a nominal burden (VA) higher than or equal to 3.75VA.
356.xxx Warning [356.xxx] License: <All frequencies support> is missing! Only 60 Hz nominal
frequency is supported.
Reason: The license required to use all frequencies is not available.
Solution: Measurements are only possible for 60 Hz. Purchase a corresponding license
if you want to perform testing with other frequencies.
357.xxx Note [357.xxx] License: <P cores support> is missing! Only metering CTs can be
measured.
Reason: The license required to perform testing of protection cores is not available.
Solution: Testing is only possible for metering cores. Purchase a corresponding license
if you want to perform testing of protection cores.
358.xxx Warning [358.xxx] License: <M cores support> is missing! Only protection CTs can be
measured.
Reason: The license required to perform testing of metering cores is not available.
Solution: Testing is only possible for protection cores. Purchase a corresponding license
if you want to perform testing of metering cores.
360.xxx Note [360.xxx] No class assessments will be made, because one or more of the settings
marked by a star ('?*' or '*') "are not defined.
Reason: Some of the assessment-relevant settings are not defined.
Solution: Make sure that all settings that are relevant for assessment (marked by '?*' or
'*') are defined.
400.xxx Warning [400.xxx] You cannot make a multi-ratio measurement without a CT SB2 switch
box!
Reason: No CT SB2 is connected when starting a multi-ratio measurement.
Solution: Connect the CT SB2 to the CT Analyzer before starting a multi-ratio test.
401.xxx Warning [401.xxx] CT SB2 switch box is disconnected!
Reason: The CT SB2 is not properly connected to the CT Analyzer.
Solution: Restore proper connection between the CT SB2 and the CT Analyzer and
restart your test.
402.xxx Warning [402.xxx] CT SB2 switch box communication error.
Reason: Communication between the CT SB2 and the CT Analyzer failed.
Solution: Restore proper connection between the CT SB2 and the CT Analyzer and
restart your test.