EasyManua.ls Logo

Omron 3G3M1-A4004-ECT - Page 662

Omron 3G3M1-A4004-ECT
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Index
(hex)
Sub-
index
(hex)
Pa-
rame-
ter No.
Function name Monitor or data range
Default
data
Set-
ting
dur-
ing
RUN
Unit
PDO
map
1F E30 Frequency Arriv-
al Detection
Width (FAR1/
F
AR2/FAR3/
FDT3/FDT4)
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.0 to 10.0
2.5
Hz Possible
20 E31 Frequency De-
tection Level1
(FDT1/FDT3)
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
5.0 to 590.0
60.0
Hz Possible
21 E32 Frequency De-
tection Hystere-
sis Width (FDT1/
FDT2)
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
5.0 to 590.0
1
Hz Possible
23 E34 Overload early
warning 2 Level
(OL2)
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.00: Disable
0.01 to 176.0
21
A Possible
24 E35 Overload early
warning 2 Detec-
tion Timer (OL2)
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.01 to 600.00
10
s Possible
25 E36 Frequency De-
tection Level 2
(FDT2/FDT4)
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
5.0 to 590.0
60.0
Hz Possible
26 E37 1st Overload
Early W
arning
Detection Level
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.00: Disable
0.01 to 176.0
21
A Possible
27 E38 1st Overload
Early Warning
Detection T
imer /
Low Current de-
tection level (OL,
LOC)
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.01 to 600.00
10
s Possible
28 E39 Display Coeffi-
cient 1 for T
rans-
port T
ime / Auxili-
ary Display Coef-
ficient 1 for
Speed Monitor
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.000 to 9,999
1
--- Possible
32 E49 Torque Com-
mand Monitor
Polarity Selection
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0: Torque polarity
1: Plus for driving, minus for braking
1
--- Possible
Appendices