141
DeviceNet Explicit Messages Appendix 1
Input Monitor
Status for
Tota l ON
Time or Con-
tact Opera-
tion Counter
Read
Read Reads the set
value for the total
ON time (unit: s) or
number of contact
operations (unit:
operations) of the
input (1 to 12)
specified by the
instance ID.
0E hex 3D hex 01 to 0C
hex
67 hex 1 byte
00 hex: Within
range
01 hex: Over
range (over the
monitor value)
Safety Input
Cause of
Error Informa-
tion Read
Read Reads the cause
for the normal flag
(1 to 12) specified
by the Instance ID
turning OFF.
0E hex 3D hex 01 to 0C
hex
6E hex 0: No error
01 hex: Con-
figuration invalid
02 hex: External
wiring error
03 hex: Internal
input failure
04 hex: Two-input
logic discrepancy
05 hex: Error in
the other dual
channel input
Explicit
message
Read/
write
Function Command Response
Service
Code
Class
ID
Instance
ID
Attribute
ID
Data size

Table of Contents