143
DeviceNet Explicit Messages Appendix 1
Output Moni-
tor Status for
Tota l ON
Time or Con-
tact Opera-
tion Counter
Read
Read Reads the set
value for the total
ON time or number
of contact opera-
tions of the output
(1 to 8) specified by
the instance ID.
0E hex 3B hex 01 to 08
hex
67 hex - 1 byte
00 hex: Within
range
01 hex: Over
range (over the
monitor value)
Safety Out-
put Cause of
Error Informa-
tion Read
Read Reads the cause
for the normal flag
(1 to 8) specified by
the Instance ID
turning OFF.
0E hex 3B hex 01 to 08
hex
6E hex 0: No error
01 hex: Con-
figuration invalid
02 hex: Overcur-
rent detected
03 hex: Short-
circuit detected
04 hex: Output
ON error
05 hex: Error in
the other dual
channel output
06 hex: Internal
relay relevant cir-
cuit error
07 hex: Relay
failure
08 hex: Dual
channel violation
09 hex: Cross
connection
detected
0A hex: EDM
error
Explicit
message
Read/
write
Function Command Response
Service
Code
Class
ID
Instance
ID
Attribute
ID
Data size