251
Advanced Function Setting Level Section 5-10
The output is turned OFF when switching to the initial setting level, com-
munications setting level, advanced function setting level, or calibration
level.
If an auxiliary output is set to close in alarm, the output is kept closed. If it
is set to open in alarm, it is kept open.
Related Parameters
Bank * alarm value 1 to 3 (bank setting level): Page 211, 212, 213
Bank * alarm value upper limit 1 to 3 (bank setting level): Page 212, 213, 214
Bank * alarm value lower limit 1 to 3 (bank setting level): Page 212, 213, 214
Alarm 1 to 3 type (initial setting level): Page 231 to 234
Standby sequence reset: Page 244, Auxiliary output * open in alarm: Page
245, HB ON/OFF: Page 246, Alarm 1 to 3 hysteresis: Page 233 (advanced
function setting level)
Event input assignment 1 to 4 (initial setting level): Page 238
HB ON/OFF: Page 246, PF setting: Page 273 (advanced function setting
level)
This parameter sets the key pressing time required to move to the protect
level from the operation level, the adjustment level, bank setting level, PID
setting level, or monitor/setting item level.
Related Parameters
Operation/adjustment protect, Initial setting/communications protect, Setting
change protect (protect level): Page 172
When this parameter is set to ON, the output assigned for alarm 1 turns
ON for input errors.
Note For details on input errors, refer to Error Displays on page 304.
The alarm 1 output is an OR output between alarm 1, HB alarm/HS
alarm, heater overcurrent alarm, and input error.
Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
Setting range Default
on: Enabled, off: Disabled off
Setting
See
See
prlt Move to Protect Level Time
Setting range Unit Default
1 to 30 Second 3
Function
Setting
See
See
sero Input Error Output
Alarm 1 must be assigned, but not to
a work bit output.
Function
Setting

Table of Contents