Section 8 Setting data
8-38
Setting data
• This sets the upper- and lower-limit of remote SP. The remote SP
upper limit is set with respect to the upper input range limit of input
2, and the remote SP lower limit is set with respect to the lower input
range limit of input 2. For example, if the input 2 type is 4 to 20 mA,
the remote SP upper limit is set with respect to 20 mA and the
remote SP lower limit is set with respect to 4 mA.
• If the input type, temperature units, and scaling of input 1 are
changed, the settings are changed to the upper and lower limits of
the sensor.
• The decimal point position depends on the selected sensor. For
analog input, the decimal point position depends on the "Decimal
point position" setting.
Note that the SP limits are in effect, and therefore if the input remote
SP is above or below the SP limits, the SP will be clamped to the
upper or lower limit.
* During cascade control only Ch2 is displayed.
The operation of E5AR/ER control functions and alarms is based on the input
values. If a value greater than "inp.2: Scaling input value 2" is set for "inp.1:
Scaling input value 1," operation will work in the opposite direction of the
display values. The user must confirm compatibility with devices. For details,
refer to "4.4 Setting the input type" (P.4-8).
Remote SP upper limit
Remote SP lower limit
rsph
rspl
Control with remote SP
*
Important
l.0
Function
Remote SP upper limit
20
Input (mA)
Using input type of 4 to 20 mA
4
RSP
Remote SP lower limit
Setting
Setting data Setting range Units Default value
Remote SP
upper limit
Temperature:
Lower limit of sensor set-
ting range to upper limit of
sensor setting range
Analog:
Smaller of 99999 and "dis-
play value equivalent to
upper input limit" to
smaller of 99999 and "dis-
play value equivalent to
upper input limit"
EU 1300.0