2 Design
Grid Connect Photovoltaic Inverte KP100L-OD-USER’S MANUAL
2-4 Wiring
2
(4) Insert wire in the interior of AC terminal block, and tighten by a flathead screwdriver.
(Tightening torque :1.2 to1.8 Nm)
(5) Tighten the cap of the cable clamp surely.
When tightening the cable clamp is insufficient, the effect of the waterproof is not achieved.
L1 L2 L3 N PE