9-43
9 Details on Servo Parameter Objects
G5-series AC Servomotors and Servo Drives User’s Manual (with Built-in EtherCAT Communications)
9-6 Extended Objects
9
Set the Main Power Supply Undervoltage Error detection time.
The main power supply OFF detection is disabled if this object is set to 2000.
Set the torque limit for immediate stops.
Set the torque limit for the following cases.
Drive prohibition deceleration with the Stop Selection for Drive Prohibition Input (3505 hex) set to 2.
When decelerating and the Disable operation option code (605C hex) is 5 or 4
When decelerating and the Shutdown option code (605B hex) is 5 or 4
The normal torque limit is applied if this object is set to 0.
Set the value in units of 1% of the rated torque (100%).
Set the overload detection level.
When the object is set to 0, the setting is 115%.
If 115 or higher is set, a value of 115% will be used.
Set the value in units of 1% of the rated torque (100%).
Set the overspeed detection level.
The overspeed detection level setting is 1.2 times the maximum motor rotation speed if this object is
set to 0.
This object should normally be set to 0. The setting should be changed only when it is necessary to
lower the overspeed detection level.
The set value of this object is limited to 1.2 times the maximum motor rotation speed.
The detection margin of error for the set value is ±3 r/min for a 5-core absolute encoder and
±36 r/min for a 5-core incremental encoder.
Set the allowable operating range for the position command input range.
If the set value is exceeded, and Overrun Limit Error (Error No. 34.0) will occur.
Refer to 7-3 Overrun Protection on page 7-11.
3509 hex
Momentary Hold Time
Setting range 70 to 2000 Unit ms Default setting 70 Data attribute C
Size 2 bytes (INT16) Access RW PDO map Not possible.
3511 hex
Immediate Stop Torque
Setting range 0 to 5000 Unit 0.1% Default setting 0 Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
3512 hex
Overload Detection Level Setting
Setting range 0 to 500 Unit % Default setting 0 Data attribute A
Size 2 bytes (INT16) Access RW PDO map Not possible.
3513 hex
Overspeed Detection Level Setting
Setting range 0 to 20000 Unit r/min Default setting 0 Data attribute A
Size 2 bytes (INT16) Access RW PDO map Not possible.
3514 hex
Overrun Limit Setting
Setting range 0 to 1000 Unit 0.1 rotation Default setting 10 Data attribute A
Size 2 bytes (INT16) Access RW PDO map Not possible.
All
All
All
All
csp
pp
hm