9-55
9 Details on Servo Parameter Objects
G5-series AC Servomotors and Servo Drives User’s Manual (with Built-in EtherCAT Communications)
9-7 Special Objects
9
Set the time to indicate the node address when the control power is turned ON.
Set the condition for torque limit output during torque control.
Explanation of Set Value
Select to enable or disable the backlash compensation during position control. Set the compensation
direction when compensation is enabled.
Refer to 7-4 Backlash Compensation on page 7-13.
Explanation of Set Value
Set the backlash compensation amount during position control.
Refer to 7-4 Backlash Compensation on page 7-13.
Set the backlash compensation time constant for position control.
Refer to 7-4 Backlash Compensation on page 7-13.
3701 hex
Power ON Address Display Duration Setting
Setting range 0 to 1000 Unit 100 ms Default setting 0 Data Attribute R
Size 2 bytes (INT16) Access RW PDO map Not possible.
3703 hex
Torque Limit Flag Output Setting
Setting range 0 to 1 Unit Default setting 0 Data Attribute A
Size 2 bytes (INT16) Access RW PDO map Not possible.
Set value Description
0 On by the torque limit value including the torque command value.
1 On by the torque limit value excluding the torque command value.
3704 hex
Backlash Compensation Selection
Setting range 0 to 2 Unit Default setting 0 Data Attribute C
Size 2 bytes (INT16) Access RW PDO map Not possible.
Set value Description
0 Disable backlash compensation.
1 Compensate for backlash at first forward operation after the servo turns ON.
2 Compensate for backlash at first reverse operation after the servo turns ON.
3705 hex
Backlash Compensation Amount
Setting range 32768 to
32767
Unit
Command unit
Default setting 0 Data Attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
3706 hex
Backlash Compensation Time Constant
Setting range 0 to 6400 Unit 0.01 ms Default setting 0 Data Attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
All
cst
csp
pp
hm
csp
pp
hm
csp
pp
hm