6-20
Set the frequency detection level in n58.
n58 Frequency Detection Level Changes during
operation
No
Setting
range
0.0 to 400 (Hz) Unit of
setting
0.1 Hz
(see note)
Default setting 0.0
Note The
value will be set in
0.1-Hz increments if the frequency is less than 100 Hz and
1-Hz increments if the frequency is 100 Hz or over.
Frequency Detection Level 1
Output
frequency
Reset width –2 Hz
n58 (Frequency
detection level)
Time
Frequency
detection level 1
Time
Frequency Detection Level 2
Output
frequency
Reset width +2 Hz
n58 (Frequency
detection level)
Time
Frequency
detection level 2