9-8
Pa-
ram-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of set-
ting
Set-
ting
range
DescriptionName
n40 Multi-func-
tion output
Used to select the functions of multi-function output
terminals.
0 to 7,
10 to
1 1 No 5-22
(MA/MB
and MC out-
-
Set
value
Function Description
17
put term
-
nals)
0
Fault output
ON: Fault output (with pro-
tective function working)
1 Operation in
progress
ON: Operation in progress
2 Frequency
detection
ON: Frequency detection
(with frequency reference
coinciding with output fre-
quency)
3 Idling ON: Idling (at less than
min. output frequency)
4 Frequency
detection 1
ON: Output frequency y
frequency detection level
(n58)
5 Frequency
detection 2
ON: Output frequency x
frequency detection level
(n58)
6 Overtorque
being moni
-
tored (NO-
contact out-
put)
Output if any of the follow-
ing parameter conditions is
satisfied.
n59: Overtorque detection
function selection
n60: Overtorque detection
7 Overture be-
ing moni
-
tored (NC-
contact out-
put)
level
n61: Overtorque detection
time
NO contact: ON with
overtorque being detected
NC contact: OFF with
overtorque being detected
8
Not used ---
9
10 Alarm output ON: Alarm being detected
(Nonfatal error being de-
tected)
11 Base block
in progress
Base block in progress (in
operation with output shut-
off)
12 RUN mode ON: Local mode (with the
Digital Operator)
13 Inverter
ready
ON: Inverter ready to oper-
ate (with no fault detected)
14 Fault retry ON: Fault retry
15 UV in prog-
ress
ON: Undervoltage being
monitored
16 Rotating in
reverse
direction
ON: Rotating in reverse
direction
List of Parameters Chapter