9-11
Pa-
rame-
ter
No.
Refer-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of set-
ting
Set-
ting
range
DescriptionName
n62 UP/DOWN
command
frequency
memory
Used to store the adjusted frequency
reference with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s
or more.
0, 1
1 0 No 6-21
n63 Torque
compensation
gain
Used to set the gain of the torque
compensation function.
The default setting does not need any
changes in normal operation.
0.0 to
2.5
0.1 1.0 Yes 6-11
n64 Motor rated slip Used to set the rated slip value of the
motor in use.
Note Used
as the constant of the slip
com
-
pensation function.
0.0 to
20.0
0.1 Hz Varies
with
the ca-
pacity.
Yes 6-12
n65 Motor no-load
current
Used to set the no-load current of the
motor in use based on the rated motor
current as 100%.
Note Used
as the constant of the slip
com
-
pensation function.
0 to 99
1% Varies
with
the ca-
pacity.
No 6-12
n66 Slip
compensation
gain
Used to set the gain of the slip
compensation function.
Note The slip compensation function is
disabled with n66 set to 0.0.
0.0 to
2.5
0.1 0.0 Yes 6-13
n67 Slip
compensation
time constant
Used for the response speed of the slip
compensation function.
Note The default setting does not need
any changes in normal operation.
0.0 to
25.5
0.1 s 2.0 No 6-13
n68 OMRON’s control
reference use
Do not change the set value. --- --- 0 --- ---
n69 OMRON’s control
reference use
Do not change the set value. --- --- 0 --- ---
n70 OMRON’s control
reference use
Do not change the set value. --- --- 0 --- ---
n71 OMRON’s control
reference use
Do not change the set value. --- --- 2 --- ---
n72 OMRON’s control
reference use
Do not change the set value. --- --- 0 --- ---
n73 OMRON’s control
reference use
Do not change the set value. --- --- 10 --- ---
n74 OMRON’s control
reference use
Do not change the set value. --- --- 0 --- ---
n75 Low-speed
carrier frequency
reduction
selection
Used to select a function to reduce the
carrier frequency when Inverter is at low
speed.
0: Function disabled
1: Function enabled
Note Normally set n75 to 0.
0.1 1 0 No 6-4
n76 OMRON’s control
reference use
Do not change the set value --- --- rdy --- ---
n77 OMRON’s control
reference use
Do not change the set value --- --- 0 --- ---
List of Parameters Chapter