2-30
D Solderless Terminals for Control Circuit Terminals
The use of solderless terminals for the control circuit terminals is recommended be-
cause solderless terminals are easy to connect securely.
Note When using the following solderless terminal, make sure that the wire size is
0.5 mm
2
.
1.0 dia.
2.6 dia.
Model: Phoenix Contact’s A1 0.5-8 WH
(Size: mm)
D Wiring Method
1. Loosen the terminal screws with a thin-slotted screwdriver.
2. Insert the wires from underneath the terminal block
3. Tighten the terminal screws firmly to a torque of 0.5 NSm.
Note 1. Always
separate the control
signal line from the main circuit cables and other
power cables.
Note 2. Do
not solder the wires to the control
circuit terminals. The wires may not con
-
tact well with the control circuit terminals if the wires are soldered.
Note 3. The
end of each wire connected to the control circuit terminals must be stripped
for approximately 5.5 mm.
Control circuit
terminal block
Thin-slotted screwdriver
Strip the end for 5.5 mm
if no solderless terminal
is used.
Wires
Solderless
terminal or wire
without soldering
Note Applying a torque of greater
than 0.5 NSm may damage the
terminal block. If the tightening
torque is insufficient, however,
wires may be disconnected.
Design Chapter
2