5-29
5
Analog Monitor Cards: F4
Param
eter
Num-
ber
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Closed
Loop
Vector
(PM)
F4-01
Channel 1 monitor
selection Using an AO-08 option card the
possible outputs signal is 0 to
+10V only. The setting of F4-07
and F4-08 has no effect.
Sets the channel 1 item bias to
100%/10 V when the analog moni-
tor card is used.
This function is enabled when the
analog monitor card is used.
Monitor selection: Sets the number
of the monitor item to be output.
(Numerical portion  of U1-
îš…îš…)
4, 10, 11, 12, 13, 14, 25, 28, 34,
35, 39 and 40 cannot be set.
Gain: Sets the percentage of the
monitor item, which is equal to
10V output.
Bias: Sets the percentage of the
monitor item, which is equal to
0V output.
1 to 56
i
No
A
2
A
2
A
2
-
391H 6-25
AO Ch1 Select 1 to 75 - -
A
5
F4-02
Channel 1 gain
0.0 to
1000.0
100.0% Yes A A A A 392H 6-25
AO Ch1 Gain
F4-03
Channel 2 monitor
selection
1 to 56
3No
AA A -
393H 6-25
AO Ch2 Select 1 to 75 - - - A
F4-04
Channel 2 gain
0.0 to
1000.0
50.0% Yes A A A A 394H 6-25
AO Ch2 Gain
F4-05
Channel 1 output
monitor bias
-110.0
to
110.0
0.0% Yes A A A A 395H 6-25
AO Ch1 Bias
F4-06
Channel 2 output
monitor bias
-110.0
to
110.0
0.0% Yes A A A A 396H 6-25
AO Ch2 Bias
F4-07
Analog output sig-
nal level for chan-
nel 1
Selects the analog output signal
level for channel 1 (effective for
the AO-12 option card only).
0: 0 to 10V
1:-10 to +10
Using an AO-08 option card the
possible outputs signal is 0 to
+10V only. The setting of F4-07
and F4-08 has no effect.
0 or 1 0 No A A A A 397H 6-25
AO Opt Level Sel
F4-08
Analog output sig-
nal level for chan-
nel 2
0 or 1 0 No A A A A 398H 6-25
AO Opt Level Sel