22
Section 2 UPGRADING THE SYSTEM
ZN
System Manual
Section 2
Setup Methods Suited to Specific Applications
Setting the high power air volume level
13. Display [HWIND] on the main display.
14. Set the high power air volume level of
the Air Clean Unit.
Set the air volume level within 1 to 5 (default value: 5).
Set the air volume level for when the target
cleanliness is not satisfied.
For the high power air volume level, always set an air volume greater than the low power
air volume level.
Feedback will not function properly if a smaller value is set.
15. Press the ENT key.
This sets the specified air volume level.
Setting the high power time
16. Display [HTIME] on the main display.
Set the high power time.
17.
Set the high power time of the Air Clean Unit.
Set the time (s) within 0 to 999 (default value: 60).
Set the time that the high power air volume level
is to be held for.
18. Press the ENT key.
This sets the specified time.
The time that the high power air volume level is actually held is an integer multiple of the
feedback cycle (i.e. measurement cycle).
Example:
Measurement cycle: 60 s
When the high power time is set to "100 s", the actual high power time is 120 s.
19. Set the mode switch to RUN.
This starts feedback control operation.
When the setting is next used, feedback is automatically started simply by turning the Air
Clean Unit power supply ON.
2sysup.fm22ページ2007年6月28日 木曜日 午前9時17

Other manuals for Omron ZN-A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron ZN-A Series and is the answer not in the manual?

Omron ZN-A Series Specifications

General IconGeneral
BrandOmron
ModelZN-A Series
CategoryAccessories
LanguageEnglish

Related product manuals