Connection
ALM-RST input
The ALM-RST input is a signal to reset an alarm status. (The alarm will be reset at the ON edge of the input.)
To reset an alarm, turn the operation input signal OFF, and remove the cause of the alarm before turning the ALM-RST
input ON. In the case of the 3-wire mode, when both the START/STOP input and RUN/BRAKE input are being ON, the
ALM-RST input is disabled. (In the case of the 2-wire mode, when either the FWD input or the REV input is being ON, the
ALM-RST input is disabled.) If the alarm cannot be reset with the ALM-RST input, once turned o the power supply and
turn on again.
ALM-A output
ALM-RST input
START/STOP input
RUN/BRAKE input
Mot
or movement
ON
OFF
ON
OFF
ON
OFF
10 ms or more
CW CW
Stop
Alarm generation
ALM-B output
ON
OFF
10 ms or less
*
If an alarm is generated while the motor rotates, the motor will coast to a stop.
Note
Continuing the operation without removing the cause of the alarm may cause damage to equipment.
Alarms of overcurrent, EEPROM error, and CPU error cannot be reset with the ALM-RST input.
INFO-CLR input
The INFO-CLR input is a signal to reset an information status. (Information will be cleared at the ON edge of the input.)
This signal is used when the "Information auto clear" parameter is set to disable, and the information status will be reset
if it is turned ON.
Related parameters
Parameter name Description Setting range Factory setting
Information auto clear
This is a function to clear the information status automatically to turn
the INFO signal OFF when the cause of the generated information
was removed.
Disable
Enable
Enable
HMI input
The HMI input is a signal to release the function limitation of the
MEXE02
. (Factory setting ON)
When the HMI input is turned ON, the function limitation of the
MEXE02
is released.
When the HMI input is turned OFF, the function limitation is imposed.
[Functions to be limited]
Operation data, writing of parameters
I/O test
Teaching/remote operation
Clearing of records and others
Conguration
Initialization
TL input
The TL input is a signal to switch whether to enable or disable the torque limiting function. (Factory setting ON)
When the TL input is turned ON, the torque limiting function is enabled.
The maximum value of the motor output torque is limited based on the set torque limiting value.
When the TL input is turned OFF, the torque limiting function is disabled, and the maximum value of the motor output
torque will be the peak torque.