13.2 Information lists
The driver status can be checked using the unit information monitor or the status monitor of the
MEXE02
.
Information
Information bit
output signal
Cause Condition to reset and clear
Driver temperature INFO-DRVTMP
The internal temperature of the driver
increased to the setting value of the
"Driver temperature information"
parameter or higher.
The internal temperature of the driver
dropped below the setting value of
the "Driver temperature information"
parameter.
Overvoltage INFO-OVOLT
The internal voltage of the driver
increased to the setting value of the
"Overvoltage information" parameter or
higher.
The internal voltage of the driver
dropped below the setting value of the
"Overvoltage information" parameter.
Undervoltage INFO-UVOLT
The internal voltage of the driver
dropped to the setting value of the
"Undervoltage information" parameter
or lower.
The internal voltage of the driver
exceeded the setting value of the
"Undervoltage information" parameter.
Load INFO-LOAD
The detected torque of the motor
increased to the setting value of the
"Load information" parameter or higher.
The detected torque of the motor
dropped below the setting value of the
"Load information" parameter.
Speed INFO-SPD
The detected speed of the motor
increased to the setting value of the
"Speed information" parameter or
higher.
The detected speed of the motor
dropped below the setting value of the
"Speed information" parameter.
Operation data setting
error
INFO-SET-E
For the setting method of operation
data, the same setting method is
assigned in the same operation data
number.
Setting method
p.29
The setting method of the operation
data number that the same setting
method had been assigned was set
again.
Operation prohibited INFO-DRV
The operation input signal is being
ON when I/O test of the
MEXE02
or teaching/remote operation was
complete.
Conguration was executed in a state
where the motor would immediately
rotate when the assignment or the
logic level setting of input terminals
was changed.
The operation data number that the
same setting method was assigned
was selected to operate.
Setting method
p.29
The operation input signal was turned
OFF.
The setting method of the operation
data number that the same setting
method had been assigned was set
again.
The selected operation data number
was changed.
Tripmeter
*
INFO-TRIP
The rotation amount inside the driver
increased to the setting value of the
"Tripmeter information" parameter or
more.
One of the following operations was
performed, and the rotation amount
inside the driver dropped below
the setting value of the "Tripmeter
information" parameter.
The "Tripmeter information"
parameter was set again.
Tripmeter was cleared using the
MEXE02
.
Odometer
*
INFO-ODO
The integrated rotation amount inside
the driver increased to the setting
value of the "Odometer information"
parameter or more.
The "Odometer information" parameter
was set again, and the integrated
rotation amount inside the driver
dropped below the setting value of the
"Odometer information" parameter.
*
The tripmeter and odometer are saved in the non-volatile memory in the driver at intervals of one minute.
If the power supply is shut o before saving in the driver, the travel distance for one minute is not applied.