Installation and Operation Manual of the EUROMATIK.net Page 36 (40)
Navigation to the home page
Navigation to the main menu
Navigation to the info page
User login
On this page the user must login to the embedded webserver using the
user-PIN (default: 1234) or the service-PIN (default: 5678) to get access
to the device.
System information page
On this page, system information of the device is displayed, e.g. serial
number and software version. Furthermore, the logged-in user can read
the current IP address for access from the local network and the device
ID for access via the -Communication-server here.
Email notification in case of failure
Assigning a name for the device
Using the LAN connection, the EUROMATIK.net can send alarm
messages by e-mail. In the adjacent window, the email addresses of the
recipient and an optional copy-recipient are entered.
To distinguish between individual pool-facilities, it is possible to give
each EUROMATIK.net a unique name.
These settings can only be made via the LAN interface. On the touchscreen monitor of the EUROMATIK.net
these settings are not available.
Connection to building management systems
The EUROMATIK.net includes an HTTP web server, which is designed to enable the operation of the
controller from any Internet-enabled device using any standard Web browser.
The HTML pages generated by this Web server can also be accessed from the building management
system and evaluated, for example, for display on KNX visualization devices.
To control the EUROMATIK.net, the building control system must generate HTTP telegrams, like they would
have been generated by a web browser after clicking controls on HTML pages - so the building
management system must simulate the behaviour of a Web browser.
As an alternative to direct analysis of our predefined HTML pages intended for display on Web browsers,
the user can also store his own control file on the SD card in the EUROMATIK.net that supplies him with the
desired information in "customized" form. This makes the connection to the building control system
independent of any design changes to our HTML pages.
This control file must be saved as an ASCII text file with the extension ".htm" in "HTML" directory on the SD
card. The file name can be up to 8 characters. Despite the extension "HTM" this file does not necessarily
have to be a valid HTML file, formatting can be adapted to the requirements of the building control system.