FPΣ User's Manual
2.1 Features
7
Simultaneous data connections via PLC Link function and standard RS232C (1:N
communication with up to 99 stations)
RS485
RS232C
RS232C
RS232C RS232C
RS485 RS485
FPΣ
2316
FPΣ FPΣ FPΣ
1
Analog control (see page
29)
All CPU types are equipped with an analog potentiometer. It can be used in applications such
as analog timers and does not require a programming tool.
Thermistor input function (see page
31)
CPUs with product numbers ending in "TM" have a lead wire for thermistor input instead of an
analog potentiometer. Changes in the thermistor's resistance can be loaded as analog input.
Thermistors with a resistance value of 200Ω to 75kΩ can be used.
Clock/calendar function (see page
35)
If an optional backup battery is installed in the FPΣ, a clock/calendar function is available.
Positioning control using high-speed counter and pulse output (see page
100)
A high-speed counter and a pulse output function are provided as standard features. The
pulse output function supports frequencies of up to 100kHz, which allows positioning control
using a stepping or a servo motor.
Measurement using high-speed counter (see page
102)
Incremental input mode, decremental input mode, two-phase input mode,
incremental/decremental input mode, and incremental/decremental control mode are
supported.