CPU Types
FPΣ User's Manual
36
Confirm each value with [Enter].
Using a program
1. The date/time values are written to special data registers DT90054 to DT90057.
2. A value of 16#8000 is written to DT90058.
NOTE
The values can be set using the rising edge signal “P” or by changing
16#8000 to 16#0000.
To access special data registers and special internal relays, use the PLC-
independent system variables. You can insert system variables directly into
the POU body: Use the "Variables" dialog without entering a declaration in
the POU header. Please refer to the FPWIN Pro online help for detailed
information on using system variables.
EXAMPLE
Set the time to 12:00:00 on the 5th day when X0 turns to TRUE. In this example, the
values of DT90054, DT90055, and DT90058 are written using system variables.
LD Body