2-level Teaching
This is a method of setting the threshold values
(1_SL, 2_SL) by two levels (P-1, P-2) teaching.
Time
ON
P-1
1_SL
P-2
2_SL
0
OFF
Incident light intensity
9,999
Output
(L-ON)
Press the
MODE key once.
Blinking by turns.
Press the
Jog switch.
Press the
Jog switch.
Incident light
intensity for P-1.
Incident light
intensity for P-2.
Upper limit value 2_SL
Lower limit value 1_SL
The symbol
will be
displayed repeatedly.
Press the
MODE key 5 times.
Upper and lower limits have
not been correctly set.
The status condition when a sensing object is present
that can be used as a standard for the lower limit.
The status condition when a sensing object is present
that can be used as a standard for the upper limit.
2The current teaching method (green) and incident light
intensity (red) will be displayed and the amplifier will enter
the P-1 setting state.
4The amplifier has entered the P-2 setting state and
(green) will blink.
7Then the setting for upper limit value 2_SL (green) will be
displayed.
8By pressing the [MODE key] 5 times, the amplifier will return
to RUN mode (normal sensing operation).
Lower limit value 1_SL (green) and incident light intensity
(red) will be displayed.
6The display will indicate whether the upper and lower limits
have been correctly set and the setting for lower limit value
1_SL (green) will be displayed.
If (red) is blinkingthe upper and lower limits have
been set correctly.
If (red) is blinkingthe upper and lower limits have
not been set correctly.
5If the [Jog switch] is pressed while in the status condition
when a sensing object is present that can be used as a
standard for the upper limit, then the display will blink the
incident light intensity reading (red).
When using retroreflective type sensor head
Press the [Jog switch] for the sensing object that has the
least amount of interrupted light.
When using reflective type sensor head
Press the [Jog switch] for the sensing object with the
greatest incident light intensity.
3If the [Jog switch] is pressed while in the status condition
when a sensing object is present that can be used as a
standard for the lower limit, then the display will blink and
indicate the incident light intensity reading (red).
When using retroreflective type sensor head
Press the [Jog switch] for the sensing object that has the
greatest amount of interrupted light.
When using reflective type sensor head
Press the [Jog switch] for the sensing object with the lowest
intensity of incident light.
Note) Even if procedures
3
and
5
are reversed, teaching for a
sensing object with low intensity incident light will
automatically cause the setting of lower limit value 1_SL.
1Select TEACH mode by pressing the [MODE key] once.
15