When in Trouble
100
115
0.1
1
10
100
150 200 250 300 350 400 450 500 torque [100%]
time [sec]
Overload protection time characteristics (Motor type M*MA)
MAMA100W
MQMA100W – 400W
MAMA200W – 750W
MSMA1kW – 5kW
MDMA1kW – 5kW
MHMA1kW – 5kW
MFMA400W – 4.5kW
MGMA900W – 4.5kW
100
0.1
1
10
100
150 200 250 300 350 400 450 500
115
time [sec]
Overload protection time characteristics (Motor type M*MD)
MSMD50W
MSMD100W (100V)
MSMD100W (200V)
MSMD200W
MSMD400W
MSMD750W
torque [100%]
• Time characteristics of Err16 (Overload protection)
• Software Limit Function
1)Outline
You can make an alarm stop of the motor with software limit protection (Error code No.34) when the
motor travels exceeding the movable range which is set up with Pr26 (Set up of software limit) against the
position command input range.
You can prevent the work from colliding to the machine end caused by motor oscillation.
2) Applicable range
This function works under the following conditions.
Control mode
Others
Conditions under which the software limit works
• Either at position control mode or full-closed control mode
Pr02 = 0 : Position control
Pr02 = 3 : 1st control mode of Position control/Velocity control
Pr02 = 4 : 1st control mode of Position control/torque control
Pr02 = 6 : Full-closed control
(1) at Servo-ON
(2) when Pr26 (Software limit setup) is other than 0.
(3) After the last clearance of the position command input range (0 clearance), the movable range
of the motor is within 2147483647 for both CCW and CW direction.
Once the motor gets out of the (3) condition, the software limit protection will be invalidated
until the later mentioned "5) Condition under which the position command input range is
cleared" is satisfied. The position command input range will be 0-cleared when the motor gets
out of the conditions of (1) and (2).