Digiplex/DigiplexNE LCD Keypad 13n
3.2 PROGRAMMING METHODS
The following methods can be used when programming the keypad:
3.2.1 FEATURE SELECT PROGRAMMING
Some sections are programmed by enabling or disabling
options. Within the sections, numbers from [1] to [8] represent
a specific keypad option. Press the key corresponding to the
desired option and the digit will appear in the display. This
means the option is enabled. Press the key again to remove
the digit from the display thereby disabling the option. Press
[
ENTER] when options are set.
3.2.2 DECIMAL PROGRAMMING
Some sections require that a decimal value be entered. In this
method, any digit from 000 to 255 can be entered.
3.3 MODULE BROADCAST
The control panel’s Module Broadcast feature can be used to copy
the contents of one keypad to one or many other keypads.
Step 1: From Normal Mode press and hold the [0] key.
Step 2: Enter [
INSTALLER CODE] (default: 000000).
Step 3: Enter section [954] (DGP-48) / [4004] (DGP-NE96).
Step 4: Enter the [
SERIAL #] of the source keypad. The source is the
programmed keypad whose data you want to copy to other
keypads.
Step 5: Enter the [
SERIAL #] of the destination keypads. The
destination is the keypad(s) you want to program with the
source’s data. If you want to program more than one keypad
with the source’s data, enter the serial numbers of the
keypads one at a time.
Step 6: Once you have entered the serial numbers of the keypads
you want to program, press the [
ACC] key.

Table of Contents

Other manuals for Paradox DGP2-641

Question and Answer IconNeed help?

Do you have a question about the Paradox DGP2-641 and is the answer not in the manual?

Paradox DGP2-641 Specifications

General IconGeneral
BrandParadox
ModelDGP2-641
CategorySecurity System
LanguageEnglish

Summary

2.0 Installation

2.1 Connecting Keypad Zones

Describes connecting detectors or door contacts directly to the keypad's input terminal.

3.0 Programming

3.1 Entering Module Programming Mode

Provides step-by-step instructions to enter the Module Programming Mode via the control panel.

4.0 System Options

4.1 Partition Assignment

Details assigning keypads to partitions 1 through 8, with limitations for specific panels.

5.0 Features for DGP2-641 Only

6.0 Features for DGP2-641AC Only

6.1 Assigning Doors To Partitions

Assigns an access control door to one or more partitions in the alarm system.

6.3 Door Lock Options

Allows programming of door lock behavior to suit security requirements.

6.3.1 Unlock on REX (Request For Exit)

Enables unlocking the door when the REX device detects movement.

6.3.2 Door Unlocked Period

Sets the time a door remains unlatched after access or REX.

6.3.5 Door Unlocked Schedule

Determines hours, days, and holidays when a door remains unlocked without a card.

6.4 Door Left Open Options

Programs how the system reacts to a door left open.

6.4.1 Door Left Open Access Alarm

Enables an alarm if a door is not closed within a specified period after opening.

6.4.2 Door Left Open Interval Before Access Alarm

Sets the time a door can be open before triggering an Access Alarm.

6.5 Door Forced Open Options

Programs how the system reacts to a door opened without authorization.

6.5.1 Door Forced Open Access Alarm

Enables an alarm if a door is opened without a valid access signal.

6.6 Access Control PIN Entry Option

Determines if PIN entry is on the keypad or a PosiPIN reader.

6.6.1 Configuring The PosiPIN's Keypad

Steps to set the PosiPIN keypad communication format to 8-bit Wiegand.