Digiplex/DigiplexNE LCD Keypad 31n
6.4.6 BEEP TIMER FOR DOOR LEFT OPEN ALARM
SECTION [012]
This beep timer determines the amount of time the Door Left
Open Alarm will beep. Once the Door Left Open Interval (see
section 6.4.2 on page 29) has expired, the Door Left Open
Alarm (see section 6.4.5 on page 30) will be triggered. Enter
any value between 001 and 255 to determine the number of
seconds the Access Alarm will beep. Default = 5 seconds.
6.5 DOOR FORCED OPEN OPTIONS
The Door Forced Open Options allow you to program how the
system will react when an Access Control door is opened without a
“Request for Exit” or “Access Granted” signal.
6.5.1 DOOR FORCED OPEN ACCESS ALARM
SECTION [006]: OPTION [3]
If an Access Control door is opened without an Access Control
Card, a User Access Code or receiving a Request for Exit, an
Access Alarm can be generated. A Burglar Alarm can also be
generated. When the door is closed during an Access Alarm,
the Door Forced Open Restore event can be logged in the
Event Buffer.
Option [3] OFF= Door Forced Open Alarm is disabled
(default)
.
Option [3] ON = Door Forced Open Alarm is enabled.
When the Door Forced Open Alarm is disabled, the following
sections are also disabled:
Section
[004] OPTION [7] DOOR FORCED OPEN ALARM
OPTION [8] DOOR FORCED OPEN ALARM FOLLOWS
[013] BEEP TIMER FOR DOOR FORCED OPEN ALARM