Parameter Reference 15-5
AC10 Inverter
Function
Code
Function Definition Setting Range Mfr’s Value
Change
F208 Terminal two-line/three-line operation control
0: No function;
1: Two-line operation mode 1;
2: Two-line operation mode 2;
3: three-line operation mode 1;
4: three-line operation mode 2;
5: start/stop controlled by
direction pulse
0
╳
F209 Selecting the mode of stopping the motor
0: stop by deceleration time;
1: free stop
0
╳
F210 Frequency display accuracy
0.01~2.00
0.01 √
F211 Speed of digital control
0.01~100.00Hz/S
5.00 √
F212 Direction memory 0: Invalid 1: Valid 0 √
F213 Auto-starting after repowered on 0: invalid; 1: valid 0 √
F214 Auto-starting after reset 0: invalid; 1: valid 0 √
F215 Auto-starting delay time
0.1~3000.0
60.0 √
F216 Times of auto-starting in case of repeated faults
0~5
0 √
F217 Delay time for fault reset
0.0~10.0
3.0 √
F218 Reserved
F219 Write EEPORM by Modbus 1: invalid; 0: valid 1 √
F220 Frequency memory after power-down 0: invalid; 1: valid 0 √
F221-
F223
Reserved
F224
When target frequency is lower than Min
frequency
0: Stop
1: run at min frequency
1 √
F225-F
227
Reserved
F228 Application selection
0: Invalid
1: Basic speed control
2: auto/manual control
3: Stage speed control
4: Terminal control;
5: PID control;
No Macro
selected
F229~
F230
Reserved