EasyManua.ls Logo

Parker COMPAX-M /-S (L) - Page 158

Parker COMPAX-M /-S (L)
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating Instructions
COMPAX-M / -S
PLC data interface (function not available with COMPAX 1000SL)
158
Start sign "E""1110"
Function code 1: "1" "0001"
Function code 2: "3" "0011"
Parameter No. tens column
Parameter No. digits column
Assignment code: "A" "1010"
Sign "0" "0000": positive
"D" "1101": negative
Numerical value 10
6
Numerical value 10
5
Numerical value 10
4
Numerical value 10
3
Numerical value 10
2
Numerical value 10
1
Numerical value 10
0
Decimal point "C" "1100"
Numerical value 10
-1
Numerical value 10
-2
End sign "F" "1111"
Start sign "E""1110"
Function code 1: "1" "0001"
Function code 2: "4" "0100"
End sign "F" "1111"
Start sign "E""1110"
Function code 1: "1" "0001"
Function code 2: "6" "0110"
Numerical value 10
1
Numerical value 10
0
End sign "F" "1111"
Start sign "E""1110"
Sign "0" "0000": positive
"D" "1101": negative
Numerical value 10
6
Numerical value 10
5
Numerical value 10
4
Numerical value 10
3
Numerical value 10
2
Numerical value 10
1
Numerical value 10
0
Decimal point "C" "1100"
Numerical value 10
-1
Numerical value 10
-2
Numerical value 10
-3
End sign "F" "1111"
The following signs are not necessary when transferring:
Positive prefixes and initial zeros.
For whole number values: the decimal point and the figures after the decimal
point.
Modify
parameters
P1...P49
Acceptance of VP
parameter
Status query
S1...S12 (actual
values)
Status response
S1...S12 (actual
values)

Table of Contents