AS-i 3.0 PROFIBUS Gateway in Stainless Steel
PROFIBUS DP
26.9.2013
47
The GSD's default user parameter telegram is:
(DP/V1 enabled, diagnostics settings see chap. <Diagnostics>).
user byte 2
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
FD
0
CS PF APF CF
default0 0 00110
Tab. 10-11.
user byte 3
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
–0
default 0 0
Tab. 10-12.
LPF:
1: LPF will be transmitted in the diagnostics
0: LPF will not be transmitted
D:
1: Delta list will be transmitted in the diagnostics
0: Delta list will not be transmitted
F:
1: EC-flags will be transmitted in the diagnostics
0: EC-flags will not be transmitted
FD:
If this bit is set, the PROFIBUS diagnostics is refreshed only if the
PROFIBUS norm dictates this ("freeze diagnostics"). In doubt the
data of the PROFIBUS masters diagnostics are not up to date.
CS:
1: ExtDiag will be set if the LCS is not empty
0: ExtDiag will not be set if the LCS is not empty
PF:
1: ExtDiag will be set if there is a periphery fault at the AS-i line
0: ExtDiag will not be set.
APF:
1: ExtDiag will be set if there is an AS-i power fail
0: ExtDiag will not be set.
CF:
1: ExtDiag will be set if there is a configuration error
0: ExtDiag will not be set.
80
16
00
16
00
16
0B
16
06
16
00
16

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pepperl+Fuchs AS-I 3.0 PROFIBUS and is the answer not in the manual?

Pepperl+Fuchs AS-I 3.0 PROFIBUS Specifications

General IconGeneral
BrandPepperl+Fuchs
ModelAS-I 3.0 PROFIBUS
CategoryGateway
LanguageEnglish

Related product manuals