AS-i/PROFIBUS Gateway
Command Interface
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Issue date - 21.12.2005
35
8.2.1.8 Read 16 Kanäle 16-Bit-Slave in.Data (OP_RD_16BIT_IN_CX)
With this command, the 16 channels of the 16-bit input-data for slaves with succe-
sive addresses according to slave profile (S-7.3, S-7.4, S-7.5, S-7.A.8, S.A.9, S-
7.A.A) can be read
8.2.1.9 Write 16 Kanäle 16-Bit-Slave out.Data (OP_WR_16BIT_IN_CX)
With this command, the 16 channels of the 16-bit input-data for slaves with succe-
sive addresses according to slave profile (S-7.3, S-7.4, S-7.5, S-7.A.8, S.A.9, S-
7.A.A) can be written.
Request
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1 4C
16
2 T – circuit
3 1. slave
4 1. channel
Response
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1 4C
16
2 T result
3 1. slave, channel 1, high byte
4 1. slave, channel 1, low byte
… …
33 16. channel, high byte
34 16. channel, low byte
Request
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1 4D
16
2 T circuit
3 1. slave
4 1. channel
5 1. slave, 1. channel, high byte
6 1. slave, 1. channel, low byte
… …
35 16. channel, high byte
36 16. channel, low byte
Response
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1 4D
16
2 T result