8.2.4.11 Read Parameter (READ_PI: Read_Parameter)
This call returns the current parameter value (actual parameter) of an AS-i slave
sent by the AS-i/PROFIBUS gateway. This value must not be confused with the
parameter echo that is supplied by the AS-i slave as a response to the write_p job.
This command can not be used for a directly reading of an AS-i parameter out of
an AS-i slave.
Meaning of bit B:
B = 0Single AS-i slave or A-slave
B = 1B-slave
8.2.4.12 Set_Permanent_Parameter (SET_PP)
With this call, a parameter value for the specified AS-i slave is configured. The val-
ue is stored permanently in the EEPROM of the gateway.
The configured parameter value is transferred only when the AS-i slave is activat-
ed after turning on the power supply on the AS-i/PROFIBUS gateway.
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1 03
16
2 T circuit
3 B slave address
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1 03
16
2 T result
3 PI
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1 43
16
2 T circuit
3 B slave address
4 PP
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1 43
16
2 T result

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pepperl+Fuchs VBG-PB-K25 and is the answer not in the manual?

Pepperl+Fuchs VBG-PB-K25 Specifications

General IconGeneral
BrandPepperl+Fuchs
ModelVBG-PB-K25
CategoryGateway
LanguageEnglish

Related product manuals