Display Description Remedy
0B8D A synchronous interrupt was illegally initiated. Initiate synchronous interrupts in the synchro-
nous modes only.
0B8F Overflow of the IPMS input FIFO. A data area was accessed with a
data width which is smaller than the data consistency defined for
this area.
Only access data areas with a data width that is
equal to the full data consistency defined for this
area.
0BD2 The bus warning time has elapsed. No data cycle could be trans-
mitted within the set bus warning time.
Check the system or increase the bus warning
time with the Set_Value_Request service.