Technical Details
Operating Manual PNOZ m1p (ETH)
20878-EN-16
34
Environmental data 773100 773103 773104 773105
Ambient temperat-
ure
In accordance
with the standard EN 60068-2-14 EN 60068-2-14 EN 60068-2-14 EN 60068-2-14
Temperature
range 0 - 60 °C 0 - 60 °C -25 - 60 °C -25 - 60 °C
Forced convec-
tion in control
cabinet off 55 °C 55 °C – –
Storage temperature
In accordance
with the standard EN 60068-2-1/-2 EN 60068-2-1/-2 EN 60068-2-1/-2 EN 60068-2-1/-2
Temperature
range -25 - 70 °C -25 - 70 °C -25 - 70 °C -25 - 70 °C
Climatic suitability
In accordance
with the standard
EN 60068-2-30, EN
60068-2-78
EN 60068-2-30, EN
60068-2-78
EN 60068-2-30, EN
60068-2-78
EN 60068-2-30, EN
60068-2-78
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during
operation
Not permitted Not permitted
Short-term (only
with separated ex-
tra low voltage)
Short-term (only
with separated ex-
tra low voltage)
EMC EN 61131-2 EN 61131-2 EN 61131-2 EN 61131-2
Vibration
In accordance
with the standard EN 60068-2-6 EN 60068-2-6 EN 60068-2-6 EN 60068-2-6
Frequency 10,0 - 150,0 Hz 10,0 - 150,0 Hz 5,0 - 500,0 Hz 5,0 - 500,0 Hz
Acceleration 1g 1g 1g 1g
Broadband noise
In accordance
with the standard – – EN 60068-2-64 EN 60068-2-64
Frequency – – 5 - 500 Hz 5 - 500 Hz
Acceleration – – 19 m/s² rms 19 m/s² rms
Corrosive gas check
SO2: Concentra-
tion 10ppm, dur-
ation 10days,
passive – – DIN V 40046-36 DIN V 40046-36
H2S: Concentra-
tion 1ppm, dura-
tion 10days,
passive – – DIN V 40046-37 DIN V 40046-37
Shock stress
In accordance
with the standard EN 60068-2-27 EN 60068-2-27 EN 60068-2-27 EN 60068-2-27
Acceleration 15g 15g 15g 15g
Duration 11 ms 11 ms 11 ms 11 ms
Max. operating
height above sea
level 2000 m 2000 m 2000 m 2000 m