Safety
OperatingManualPNOZs50
1002194EN02
11
}
Toshutdowntheinductiveloadsafely,thefastshutdownmustbeactivatedafterthe
slowshutdown.Thatwaytheloadhasadualpoleshutdown.
Measurestopreventunexpectedstartup
}
Appropriatemeasuresmustbetakentopreventunexpectedstartuporunexpected
movementsfromplantstandstill.
Wiringmeasures
}
TheeffectivecurrentatterminalsB1/B2tosupplythepowercircuitsmustnotexceed
10A.Thecablesmustbefittedwitha10Afuse,characteristicB/C.
}
Thecablesfortheunit'ssupplyvoltage(A1/A2)mustbefittedwitha4Afuse,charac
teristicB/C.
}
Thewiringmustbedesignedtoachievesufficientnoiseimmunityandprotection
againstemissionsintermsofEMC.PleasealsorefertoDINEN602041(Electrical
equipmentofmachines).
}
Appropriatewiringmeasuresshouldbetakentoavoidearthfaultsandshortsbetween
contacts.
Display
}
Thecorrectdisplayofconfigurationdataandmessagesarepartofthedevice'ssafety
concept.Ifthedisplayisfaulty(e.g.pixelsaremissing,faultylettersornumbers),the
devicemustbetakenoutofservice.
Themachinemanufacturermustcheckandverifythefunctionalityoftheemployedsafety
functions.
}
Thesafetyfunctionsmayonlybecheckedbyqualifiedpersonnel.
Thesafetyfunctionmustbechecked
}
Afterinitialcommissioning
}
Afterchangingtheconfigurationofthesafetyfunctions
}
AfterswappingthePNOZs50orconnectedequipment
Afullcheckcomprises
}
Properexecutionoftheemployedsafetyfunctions
}
Inspectionoftheparameters
Theresultofthecheckoneachsafetyfunctionmustbedocumentedinatestreport.This
testreportmustbesigned.
Regularchecks
ThePNOZs50usesappropriateteststoguaranteethatitfunctionssafely(seechapteren
titled"Functiondescription",under"Outputtest").Itdoesnottesttheentiresafetyfunction.
Youshouldcheckthisatregularintervals.Theaimoftheseregularchecksistouncover
anychangestotheplant/machine,safetyfunctionsandambientconditions.Inparticular
youshouldregularlycheckthefunctionoftheconnectedbrake.
Youmustcomplywiththerequirementsoftheapplicablenationalregulations.
Theintervalsyouselectwilldependontheapplication,theoverallsystemandtheassoci
atedriskanalysis.