EasyManua.ls Logo

Pilz PNOZ s50 - Supplementary Data and Load Limits

Pilz PNOZ s50
69 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Supplementarydata
OperatingManualPNOZs50
1002194EN02
65
10 Supplementarydata
Themax.permittedloadcurrentatthepowercircuitsO1+/O1andO2+/O2dependson
the
}
Ambienttemperature.
}
DistancebetweenthePNOZs50andadjacentdevices.
}
Numberofpowercircuitsconnected(oneortwo).
}
SizeofthesupplyvoltagetothepowercircuitsatB1/B2.
INFORMATION
Youmayneedtoconsiderthedistancefromadjacentdevices!
Ifadistanceneedtobemaintainedbetweenadjacentdevices,pleaserefer
totheinformationinthechapterentitled"Installation",under"Mountingdis
tances".
Distancere
quiredbetween
adjacent
devices
Ambienttem
perature
Numberof
powercircuits
Max.permitted
outputcurrent
atU
B1/B2
=24V
Max.permitted
outputcurrent
atU
B1/B2
=48V
Yes 45°C 1 6.5A 3.25A
Yes 55°C 1 5.5A 2.75A
Yes 45°C 2 4.5A 2.25A
Yes 55°C 2 4.0A 2.0A
No 45°C 1 6.0A 3.0A
No 55°C 1 5.0A 2.5A
No 45°C 2 4.0A 2.0A
No 55°C 2 3.5A 1.75A
UseofthedevicesinaccordancewithUL
Ambienttem
perature
Numberof
powercircuits
Max.permitted
outputcurrent
atU
B1/B2
=24V
Max.permitted
outputcurrent
atU
B1/B2
=48V
Utilisationcat
egory
45°C 1 6.5A 3.25A PilotDuty
55°C 1 5.5A 2.75A
45°C 2 4.5A 2.25A
55°C 2 4.0A 2.0A
WhenusingthedevicesinaccordancewithUL,pleasenotethefollowing:
}
TheambienttemperatureisunderstoodtobetheSurroundingAirTemperature.
}
Appropriatemeasurese.g(temperingofthecontrolcabinet)shouldbeusedtoensure
thatthestatedvaluesaremaintainedwhendevicesareinstalledwithoutadistance.