Commissioning
OperatingManualPNOZs50
1002194EN02
26
6 Commissioning
6.1 Wiring
6.1.1 Generalwiringguidelines
Note:
}
Informationgiveninthe"Technicaldetails"mustbefollowed.
}
Usecopperwirethatcanwithstand75°C.
}
Thewiringmustbedesignedtoachievesufficientnoiseimmunityandprotection
againstnoiseemissionsintermsofEMC.PleasealsorefertoDINEN602041(Elec
tricalequipmentofmachines).
Inputs
}
Appropriatewiringmustbeusedtoexcludeshortcircuitsbetweentheinputsortoa
supplyline!
Outputs
}
Ifshortcircuitsoccurbetweenthecablefromtheoutputtotheloadandasupplyline,it
willnolongerbepossibletoswitchofftheload.
Possibleremedy:Excludetheerrorbyusingseparatemulticorecableforsupply
voltages
}
Useappropriatewiringtoexcludeshortcircuitsbetweentheoutputs!
6.1.2 Pinassignment
FemaleconnectorX1 Terminal Description
A2 A2 S36 S35 S11 S11 T1 T0
x
1
A2 Referencepotentialfor
Device'ssupplyvoltage
Inputs
Faultsignalandstatusoutputs
S36 Standardinputforslowshutdown,power
circuit2
S35 Standardinputforslowshutdown,power
circuit1
S11 Voltageoutput24VDC
S11 Voltageoutput24VDC
T1 Testpulseoutput1
T0 Testpulseoutput0