Parameter
number
Parameter name Description Default value Allowed range
4 PDP control On: The dryer tries to
follow the set point.
Off: only display the
PDP. The dryer will run
at the lowest possible
dewpoint.
Off On or Off
5 Dewpoint setpoint Fixes the target for the
PDP
Based on the model
of dryer:
-20 °C (-4 °F)
-40 °C (-40 °F)
-70 °C (-100
°F)
Maximum value: -10 °C
(+14 °F)
Minimum value:
-20 °C (-4 °F)
-40 °C (-40 °F)
-70 °C (-100 °F)
based on the model of
dryer.
6 PDP temp in °F Selects the temperature
unit
Off On or Off
All other parameters are protected by a password and need no modification.
PDP Sensor retrofit
PDP sensor retrofit kit number: 8092 2617 80
Press the Enter button for at least 2 seconds to return to the selection menu.
For controllers with software version 1.02.x and higher, use password: 4321. Please note that the
password has to be entered from the right to the left.
To edit the PDP parameters:
1. Go to parameter number 8: Enable PDP sensor
Set parameter: ‘ON’
2. Go to parameter number 4: PDP control
Choose preferred behaviour.
3. Go to parameter number 5
Modify and confirm preferred setpoint.
For controllers using software version 1.01.x, contact your supplier.
Service
After servicing, press ENTER for at least 5 seconds to confirm that the service has been
executed.
Instruction book
22 2920 7111 23