OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 40
********************************************************************************************************
The next group of settings pertain to 3 Product SetPoint Firmware Only (Vxx99xx or Vxx00xx) and are used to
configure the numbered Product SetPoints.
SP1 P VoL Product SetPoint (Percent Volume): A Product SetPoint represents a range defined as a
SP2 P VoL combination of two values: (1) the threshold is a numeric value that defines the percent volume
SP3 P VoL that must be met or exceeded to be considered in alarm and (2) the direction of over (>) or
under (<) determines whether the range includes everything above or below the threshold. For
example, a value of Over 90% means the alarm will activate when the product volume increases
to 90% of tank capacity and remains in alarm when above 90% tank capacity. Setting the
threshold to zero disables the SetPoint.
Entry Type: 3 digit numeric as a percent of total Tank Capacity.
Range Limits: Over, Under 0.0-99.9%
Default/Initialized value: SP1: >95.0: 95% Gross Volume of Tank Capacity and higher
SP2: >90.0: 90% Gross Volume of Tank Capacity and higher
SP3: <20.0: 20% Gross Volume of Tank Capacity and lower
SP1 G VoL Product SetPoint (Gross Volume): A Product SetPoint represents a range defined as a
SP2 G VoL combination of two values: (1) the threshold is a numeric value that defines the percent volume
SP3 G VoL that must be met or exceeded to be considered in alarm and (2) the direction of over (>) or
under (<) determines whether the range includes everything above or below the threshold. For
example, a value of Over 9000 Gallons/Liters means the alarm will activate when the product
volume increases to 9000 Gallons/Liters and remains in alarm when above 9000 Gallons/Liters.
Setting the threshold to zero disables the SetPoint.
Entry Type: 3 digit numeric as a percent of total Tank Capacity.
Range Limits: Over, Under 0-999,999
Default/Initialized value: >000000
SP1 LEVEL Product SetPoint (Level): A Product SetPoint represents a range defined as a combination
SP2 LEVEL of two values: (1) the threshold is a numeric value that defines the percent volume that must be
SP3 LEVEL met or exceeded to be considered in alarm and (2) the direction of over (>) or under (<)
determines whether the range includes everything above or below the threshold. For example,
a value of Over 90 inches/2300 mm means the alarm will activate when the product level
increases to 90 inches/2300 mm and remains in alarm when above 90 inches/2300 mm. Setting
the threshold to zero disables the SetPoint.
Entry Type: 3 digit numeric as a percent of total Tank Capacity.
Range Limits: Over, Under 0.0-1999.9
Default/Initialized value: >0000.0
SP1 Name SetPoint Name: The selected name is used to identify the purpose of the Product SetPoint
SP2 Name and is documented in the Alarm Log and visible through Serial A-D, Modem, and Network
SP3 Name Communications interfaces
Entry Type: select list
Range Limits: See below table
Default/Initialized value: SP1: HiHigh
SP2: High
SP3: Lo
LEVEL
Level
High
High
HiHigh
High-high
OuerfL
Overfill
Lo
Low
Lo Lo
Low-Low
CritHi
Critical High
CritLo
Critical Low
SP1 Horn SetPoint Horn: Indicates whether the integrated horn activates for the specified Product
SP2 Horn SetPoint. Logging and Printing are unaffected by this setting.
SP3 Horn Entry Type: select list
Range Limits: Yes, No
Default/Initialized value: Yes
This ends the group of settings that pertain to 3 Product SetPoint Firmware Only (Vxx99xx or Vxx00xx). All settings
that follow pertain to all firmware versions unless otherwise noted.
********************************************************************************************************