PERFORMANCE AT 82°F AIR AND 80°F WATER
POOL WATER CONDENSER
(VENTED)
MODEL AW
RETURN AIR
CFM
RETURN AIR
RH (%)
MOISTURE
REMOVAL (LBS/HR)
SENSIBLE COOLING
CAPACITY (MBH)
ACC MAX. HEAT
REJECTION (MBH)
GPM
PRESSURE DROP
FT WATER
0550 900
60 11.1 13.6 31.2
4 6
50 8.5 15.6 30.1
0800 1600
60 15.7 22.1 47.5
6 10
50 11.7 24.9 45.7
1200 1700
60 20.8 26.9 57.9
10 24
50 15.5 30.5 55.5
1400 2300
60 26.0 38.4 76.6
10 8
50 18.8 43.4 73.6
1800 2500
60 30.9 41.8 89.1
12 12
50 22.9 47.8 86.1
2600 3300
60 45.1 54.6 120.9
13 6
50 35.0 60.6 115.6
3500 4300
60 59.7 78.9 170.0
24 17
50 44.2 89.8 163.4
4000 4500
60 70.4 87.6 197.5
28 24
50 52.4 100.1 189.3